Ethernet IP / Modbus TCP Gateway

Communicate with Modbus RTU devices on an Ethernet IP or Modbus TCP Network

VS7072

The Anybus Communicator for EtherNet/IP and Modbus-TCP allows the user to take almost any serial device and have it communicate to an EtherNet/IP or Modbus-TCP network. The Anybus Communicator is conformance tested to current Ethernet/IP and Modbus-TCP specifications guaranteeing network compatibility. It acts as a device adapter on the network and presents the serial data to the master controller as easily processed I/O data. The 2-port Ethernet switch allows daisy chaining and removes the need for external switches.

User Manual (PDF 4.16 MB)

Installation Leaflet (PDF 203 KB)

EDS Files (ZIP 16 KB)

Configuration Manager (ZIP 3.32 MB)

Call us for pricing and delivery

Features
Dual 10/100 MBit twisted pair RJ45 connection
Multi-drop to up to 31 nodes
CE, UL & cUL marked
TCP/IP settings configurable with web-page, Configuration Tool, DHCP or ARP
Modbus/TCP class 0, class 1 and partially class 2 slave functionality
Transformer isolated Ethernet interface
Email functionality (SMTP)
User downloadable web pages through FTP server
1.4 Mbyte storage space on Flash disk
Support for IPconfig utility for easy TCP/IP setup
Serial network configuration with Configuration Manager tool
SSI sripts used for easy display/control of process data on webpages
DIN-rail mountable - PE via DIN-rail
EtherNet/IP Adapter Class Device
Specifications

Size

4.72" x 2.95" x 1.06" (120 mm x 75 mm x 27 mm)

Power Supply

24V +/-20%

Temperature

32 to 131°F (0 to +55°C)

Power Consumption

max 280mA

Baud Rate (Profinet IO)

100 Mbit

Sub Baud Rate (Modbus RTU)

1.2, 2.4, 4.8, 9.6, 19.2, 35.7, 38.4, 57,6 kbit/s

I/O Input

512 bytes

I/O Output

512 bytes

Enclosure Rating

IP20

Profile Support

Modbus TCP Class 0, 1, and partial Class 2 server functionality, EtherNet/IP level 2 I/O Server CIP (ControlNet & DeviceNet)

Support Features

Modbus-TCP, EtherNet/IP, Webserver, FTP, Email, DHCP, ARP, Telnet

Configuration Method

Configuration Manager for Windows

Serial telegrams

Max 100 different configurable telegrams

Modbus RTU command

Max 50 (request and response)

Application Interface

RS232, RS422, RS485

Galvanic isolation

Standard for both bus side and serial side

Included accessories

Cd with software and User Manuals, Configuration Cable RS232, Dsub with screw terminals for Sub-Network, Installation Leaflet

Ordering Part Number

VS7072